CENTUM series provided by Yokogawa Electric Corporation are vulnerable to cleartext storage of sensitive information. If an attacker who can login or access the computer where the affected product is installed tampers the password file stored in the computer, the user privilege which CENTUM managed may be escalated. As a result, the control system may be operated with the escalated user privilege. To exploit this vulnerability, the following prerequisites must be met: (1)An attacker has obtained user credentials where the affected product is installed, (2)CENTUM Authentication Mode is used for user authentication when CENTUM VP is used. The affected products and versions are as follows: CENTUM CS 1000, CENTUM CS 3000 (Including CENTUM CS 3000 Entry Class) R2.01.00 to R3.09.50, CENTUM VP (Including CENTUM VP Entry Class) R4.01.00 to R4.03.00, R5.01.00 to R5.04.20, and R6.01.00 and later, B/M9000 CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R7.04.51 and R8.01.01 and later
Max CVSS
7.8
EPSS Score
0.04%
Published
2023-04-11
Updated
2023-04-21
A vulnerability of Uncontrolled Resource Consumption has been identified in STARDOM provided by Yokogawa Electric Corporation. This vulnerability may allow to a remote attacker to cause a denial-of-service condition to the FCN/FCJ controller by sending a crafted packet. While sending the packet, the maintenance homepage of the controller could not be accessed. Therefore, functions of the maintenance homepage, changing configuration, viewing logs, etc. are not available. But the controller’s operation is not stopped by the condition. The affected products and versions are as follows: STARDOM FCN/FCJ R1.01 to R4.31.
Max CVSS
5.3
EPSS Score
0.10%
Published
2023-12-01
Updated
2023-12-08
Stack-based buffer overflow in WTViewerE series WTViewerE 761941 from 1.31 to 1.61 and WTViewerEfree from 1.01 to 1.52 allows an attacker to cause the product to crash by processing a long file name.
Max CVSS
9.8
EPSS Score
0.19%
Published
2022-10-24
Updated
2022-10-25
CENTUM VP / CS 3000 controller FCS (CP31, CP33, CP345, CP401, and CP451) contains an issue in processing communication packets, which may lead to resource consumption. If this vulnerability is exploited, an attacker may cause a denial of service (DoS) condition in ADL communication by sending a specially crafted packet to the affected product.
Max CVSS
7.5
EPSS Score
0.12%
Published
2022-08-16
Updated
2022-08-17
Use of insufficiently random values vulnerability exists in Vnet/IP communication module VI461 of YOKOGAWA Wide Area Communication Router (WAC Router) AW810D, which may allow a remote attacker to cause denial-of-service (DoS) condition by sending a specially crafted packet.
Max CVSS
7.8
EPSS Score
0.93%
Published
2022-07-04
Updated
2022-07-11
Use of hard-coded credentials vulnerability exists in STARDOM FCN Controller and FCJ Controller R4.10 to R4.31, which may allow an attacker with an administrative privilege to read/change configuration settings or update the controller with tampered firmware.
Max CVSS
9.0
EPSS Score
0.15%
Published
2022-06-28
Updated
2024-02-13
Violation of secure design principles exists in the communication of CAMS for HIS. Affected products and versions are CENTUM series where LHS4800 is installed (CENTUM CS 3000 and CENTUM CS 3000 Small R3.08.10 to R3.09.00), CENTUM series where CAMS function is used (CENTUM VP, CENTUM VP Small, and CENTUM VP Basic R4.01.00 to R4.03.00), CENTUM series regardless of the use of CAMS function (CENTUM VP, CENTUM VP Small, and CENTUM VP Basic R5.01.00 to R5.04.20 and R6.01.00 to R6.09.00), Exaopc R3.72.00 to R3.80.00 (only if NTPF100-S6 'For CENTUM VP Support CAMS for HIS' is installed), B/M9000 CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R8.03.01). If an adjacent attacker successfully compromises a computer using CAMS for HIS software, they can use credentials from the compromised machine to access data from another machine using CAMS for HIS software. This can lead to a disabling of CAMS for HIS software functions on any affected machines, or information disclosure/alteration.
Max CVSS
8.8
EPSS Score
0.08%
Published
2022-06-28
Updated
2022-07-14
Cleartext transmission of sensitive information vulnerability exists in STARDOM FCN Controller and FCJ Controller R1.01 to R4.31, which may allow an adjacent attacker to login the affected products and alter device configuration settings or tamper with device firmware.
Max CVSS
7.9
EPSS Score
0.09%
Published
2022-06-28
Updated
2022-07-08
OS command injection vulnerability exists in CENTUM VP R4.01.00 to R4.03.00, CENTUM VP Small R4.01.00 to R4.03.00, CENTUM VP Basic R4.01.00 to R4.03.00, and B/M9000 VP R6.01.01 to R6.03.02, which may allow an attacker who can access the computer where the affected product is installed to execute an arbitrary OS command by altering a file generated using Graphic Builder.
Max CVSS
7.8
EPSS Score
0.04%
Published
2022-04-15
Updated
2022-04-22
Improper authentication vulnerability in the communication protocol provided by AD (Automation Design) server of CENTUM VP R6.01.10 to R6.09.00, CENTUM VP Small R6.01.10 to R6.09.00, CENTUM VP Basic R6.01.10 to R6.09.00, and B/M9000 VP R8.01.01 to R8.03.01 allows an attacker to use the functions provided by AD server. This may lead to leakage or tampering of data managed by AD server.
Max CVSS
9.1
EPSS Score
0.16%
Published
2022-04-15
Updated
2022-04-22
The following Yokogawa Electric products hard-code the password for CAMS server applications: CENTUM VP versions from R5.01.00 to R5.04.20 and versions from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00
Max CVSS
9.8
EPSS Score
0.20%
Published
2022-03-11
Updated
2022-03-18
The following Yokogawa Electric products contain insecure DLL loading issues. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.
Max CVSS
7.8
EPSS Score
0.06%
Published
2022-03-11
Updated
2022-03-18
CAMS for HIS Server contained in the following Yokogawa Electric products improperly authenticate the receiving packets. The authentication may be bypassed via some crafted packets: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, and Exaopc versions from R3.72.00 to R3.79.00.
Max CVSS
8.8
EPSS Score
0.10%
Published
2022-03-11
Updated
2022-03-18
CAMS for HIS Log Server contained in the following Yokogawa Electric products fails to properly neutralize log outputs: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, and Exaopc versions from R3.72.00 to R3.79.00.
Max CVSS
8.1
EPSS Score
0.08%
Published
2022-03-11
Updated
2022-03-18
'Root Service' service implemented in the following Yokogawa Electric products creates some named pipe with improper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.
Max CVSS
7.8
EPSS Score
0.04%
Published
2022-03-11
Updated
2022-03-18
CAMS for HIS Log Server contained in the following Yokogawa Electric products is vulnerable to uncontrolled resource consumption. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.
Max CVSS
8.1
EPSS Score
0.08%
Published
2022-03-11
Updated
2022-03-18
'Long-term Data Archive Package' service implemented in the following Yokogawa Electric products creates some named pipe with imporper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.
Max CVSS
7.8
EPSS Score
0.04%
Published
2022-03-11
Updated
2022-03-18
Path traversal vulnerability exists in CAMS for HIS Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.
Max CVSS
8.8
EPSS Score
0.09%
Published
2022-03-11
Updated
2022-03-18
The following Yokogawa Electric products do not change the passwords of the internal Windows accounts from the initial configuration: CENTUM VP versions from R5.01.00 to R5.04.20 and versions from R6.01.00 to R6.08.0, Exaopc versions from R3.72.00 to R3.79.00.
Max CVSS
9.8
EPSS Score
0.20%
Published
2022-03-11
Updated
2022-03-18
There is a path traversal vulnerability in CAMS for HIS Log Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, andfrom R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00.
Max CVSS
8.1
EPSS Score
0.08%
Published
2022-03-11
Updated
2022-03-18
In Yokogawa WideField3 R1.01 - R4.03, a buffer overflow could be caused when a user loads a maliciously crafted project file.
Max CVSS
9.8
EPSS Score
0.21%
Published
2022-03-18
Updated
2022-03-28
Directory traversal vulnerability in CAMS for HIS CENTUM CS 3000 (includes CENTUM CS 3000 Small) R3.08.10 to R3.09.50, CENTUM VP (includes CENTUM VP Small, Basic) R4.01.00 to R6.07.00, B/M9000CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R8.03.01 allows a remote unauthenticated attacker to create or overwrite arbitrary files and run arbitrary commands via unspecified vectors.
Max CVSS
9.8
EPSS Score
0.52%
Published
2020-08-05
Updated
2020-08-12
CAMS for HIS CENTUM CS 3000 (includes CENTUM CS 3000 Small) R3.08.10 to R3.09.50, CENTUM VP (includes CENTUM VP Small, Basic) R4.01.00 to R6.07.00, B/M9000CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R8.03.01 allows a remote unauthenticated attacker to bypass authentication and send altered communication packets via unspecified vectors.
Max CVSS
9.8
EPSS Score
0.72%
Published
2020-08-05
Updated
2020-08-12
An unquoted search path vulnerability in Multiple Yokogawa products for Windows (Exaopc (R1.01.00 ? R3.77.00), Exaplog (R1.10.00 ? R3.40.00), Exaquantum (R1.10.00 ? R3.02.00 and R3.15.00), Exaquantum/Batch (R1.01.00 ? R2.50.40), Exasmoc (all revisions), Exarqe (all revisions), GA10 (R1.01.01 ? R3.05.01), and InsightSuiteAE (R1.01.00 ? R1.06.00)) allow local users to gain privileges via a Trojan horse executable file and execute arbitrary code with eleveted privileges.
Max CVSS
7.8
EPSS Score
0.08%
Published
2019-12-26
Updated
2020-01-08
License Manager Service of YOKOGAWA products (CENTUM VP (R5.01.00 - R6.06.00), CENTUM VP Entry Class (R5.01.00 - R6.06.00), ProSafe-RS (R3.01.00 - R4.04.00), PRM (R4.01.00 - R4.02.00), B/M9000 VP(R7.01.01 - R8.02.03)) allows remote attackers to bypass access restriction to send malicious files to the PC where License Manager Service runs via unspecified vectors.
Max CVSS
10.0
EPSS Score
1.69%
Published
2019-02-13
Updated
2020-08-24
44 vulnerabilities found
1 2